DIVISION: SPECIFIED CONSTRUCTION PRODUCTS
TRADE NAME:
3M BRAND FIRE BARRIER CP-25 WB+ CAULK (REVISED)
ID NUMBER/U.P.C.:
42-0011-1354-9 - - -
ISSUED: May 21, 2001
SUPERSEDES: November 02, 2000
DOCUMENT: 06-3743-9
-----------------------------------------------------------------------------
1. INGREDIENT C.A.S. NO. PERCENT
-----------------------------------------------------------------------------
SYNTHETIC POLYMER LATEX*................ Unknown 20.0 - 30.0
ZINC BORATE HYDRATE..................... 12447-61-9 20.0 - 25.0
WATER................................... 7732-18-5 20.0 - 30.0
SODIUM SILICATE......................... 1344-09-8 10.0 - 16.0
2-ETHYLHEXYLDIPHENYL PHOSPHATE.......... 1241-94-7 5.0 - 6.0
ZINC BORATE............................. 1332-07-6 2.5 - 3.5
IRON OXIDE.............................. 1309-37-1 2.0 - 3.0
FLAME RETARDANT......................... Unknown 1.5 - 3.0
TRADE SECRET*........................... Unknown < 2.0741
CHOPPED FIBERGLASS...................... 65997-17-3 1.0 - 2.0
VINYL ACETATE........................... 108-05-4 < 0.2
FORMALDEHYDE............................ 50-00-0 < 0.03
*NJTSRN 05995500
This product contains the following toxic chemical or chemicals subject to
the reporting requirements of Section 313 of Title III of the Emergency
Planning and Community Right-To-Know Act of 1986 and 40 CFR Part 372:
ZINC BORATE HYDRATE
ZINC BORATE
VINYL ACETATE
FORMALDEHYDE
-----------------------------------------------------------------------------
Abbreviations: N/D - Not Determined N/A - Not Applicable CA - Approximately
MSDS: 3M BRAND FIRE BARRIER CP-25 WB+ CAULK (REVISED)
May 21, 2001 PAGE 2
-----------------------------------------------------------------------------
2. PHYSICAL DATA
-----------------------------------------------------------------------------
BOILING POINT:................. ca. 100 C
VAPOR PRESSURE:................ ca. 17.5 mmHg
VAPOR DENSITY:................. N/D
EVAPORATION RATE:.............. ca. .33 BuOAc=1
SOLUBILITY IN WATER:........... complete
SPECIFIC GRAVITY:.............. ca. 1.35 g/ml
PERCENT VOLATILE:.............. ca. 19.9 %
pH:............................ 7.5 - 8.0
VISCOSITY:..................... ca. 12000 poise Brookfield
MELTING POINT:................. N/D
APPEARANCE AND ODOR:
BROWN CAULK THIXOTROPIC PASTE WITH NEGLIGIBLE ODOR.
-----------------------------------------------------------------------------
3. FIRE AND EXPLOSION HAZARD DATA
-----------------------------------------------------------------------------
FLASH POINT:................... N/A
FLAMMABLE LIMITS - LEL:........ N/A
FLAMMABLE LIMITS - UEL:........ N/A
AUTOIGNITION TEMPERATURE:...... N/A
EXTINGUISHING MEDIA:
Nonflammable.
SPECIAL FIRE FIGHTING PROCEDURES:
Wear full protective clothing, including helmet, self-contained,
positive pressure or pressure demand breathing apparatus, bunker coat
and pants, bands around arms, waist and legs, face mask, and
protective covering for exposed areas of the head.
UNUSUAL FIRE AND EXPLOSION HAZARDS:
No unusual fire or explosion hazards are anticipated.
NFPA HAZARD CODES: HEALTH: 1 FIRE: 0 REACTIVITY: 0
UNUSUAL REACTION HAZARD: none
OSHA FIRE HAZARD CLASS: Not determined
-----------------------------------------------------------------------------
4. REACTIVITY DATA
-----------------------------------------------------------------------------
STABILITY: Stable
INCOMPATIBILITY - MATERIALS/CONDITIONS TO AVOID:
None known.
HAZARDOUS POLYMERIZATION: Hazardous polymerization will not occur.
-----------------------------------------------------------------------------
Abbreviations: N/D - Not Determined N/A - Not Applicable CA - Approximately
MSDS: 3M BRAND FIRE BARRIER CP-25 WB+ CAULK (REVISED)
May 21, 2001 PAGE 3
-----------------------------------------------------------------------------
4. REACTIVITY DATA (continued)
-----------------------------------------------------------------------------
HAZARDOUS DECOMPOSITION PRODUCTS:
None known.
-----------------------------------------------------------------------------
5. ENVIRONMENTAL INFORMATION
-----------------------------------------------------------------------------
SPILL RESPONSE:
Refer to other sections of this MSDS for information regarding
physical and health hazards, respiratory protection, ventilation, and
personal protective equipment. Clean up residue.
RECOMMENDED DISPOSAL:
Dispose of waste product in a sanitary landfill.
ENVIRONMENTAL DATA:
No data available.
REGULATORY INFORMATION:
Volatile Organic Compounds: N/D.
VOC Less H2O & Exempt Solvents: N/D.
Since regulations vary, consult applicable regulations or authorities
before disposal.
EPCRA HAZARD CLASS:
FIRE HAZARD: No PRESSURE: No REACTIVITY: No ACUTE: Yes CHRONIC: No
-----------------------------------------------------------------------------
6. SUGGESTED FIRST AID
-----------------------------------------------------------------------------
EYE CONTACT:
Immediately flush eyes with large amounts of water. Get immediate
medical attention.
SKIN CONTACT:
Flush skin with large amounts of water. If irritation persists, get
medical attention.
INHALATION:
If signs/symptoms occur, remove person to fresh air. If
signs/symptoms continue, call a physician.
IF SWALLOWED:
Do not induce vomiting. Drink two glasses of water. Call a physician.
-----------------------------------------------------------------------------
Abbreviations: N/D - Not Determined N/A - Not Applicable CA - Approximately
MSDS: 3M BRAND FIRE BARRIER CP-25 WB+ CAULK (REVISED)
May 21, 2001 PAGE 4
-----------------------------------------------------------------------------
7. PRECAUTIONARY INFORMATION
-----------------------------------------------------------------------------
EYE PROTECTION:
Avoid eye contact.
SKIN PROTECTION:
Avoid prolonged or repeated skin contact.
RECOMMENDED VENTILATION:
No hazards anticipated. However, provide ventilation adequate to
control odors.
RESPIRATORY PROTECTION:
Avoid prolonged breathing of vapors.
PREVENTION OF ACCIDENTAL INGESTION:
Wash hands after handling and before eating.
RECOMMENDED STORAGE:
Store away from heat. Store at temperatures above 32 degrees F (O
degrees C).
FIRE AND EXPLOSION AVOIDANCE:
Not applicable.
EXPOSURE LIMITS
INGREDIENT VALUE UNIT TYPE AUTH SKIN*
-----------------------------------------------------------------------------
SYNTHETIC POLYMER LATEX*............. NONE NONE NONE NONE
ZINC BORATE HYDRATE.................. NONE NONE NONE NONE
WATER................................ NONE NONE NONE NONE
SODIUM SILICATE...................... NONE NONE NONE NONE
2-ETHYLHEXYLDIPHENYL PHOSPHATE....... NONE NONE NONE NONE
ZINC BORATE.......................... NONE NONE NONE NONE
IRON OXIDE........................... 5 MG/M3 TWA ACGIH
as Fe
IRON OXIDE........................... 10 MG/M3 TWA OSHA
as fume
FLAME RETARDANT...................... NONE NONE NONE NONE
TRADE SECRET*........................ NONE NONE NONE NONE
CHOPPED FIBERGLASS................... 10 MG/M3 TWA 3M
AS DUST
VINYL ACETATE........................ 10 PPM TWA ACGIH
VINYL ACETATE........................ 15 PPM STEL ACGIH
VINYL ACETATE........................ 10 PPM TWA OSHA
VINYL ACETATE........................ 20 PPM STEL OSHA
VINYL ACETATE........................ 5 PPM TWA CMRG
FORMALDEHYDE......................... 0.3 PPM CEIL ACGIH
SENSITIZER
FORMALDEHYDE......................... 0.75 PPM TWA OSHA
-----------------------------------------------------------------------------
Abbreviations: N/D - Not Determined N/A - Not Applicable CA - Approximately
MSDS: 3M BRAND FIRE BARRIER CP-25 WB+ CAULK (REVISED)
May 21, 2001 PAGE 5
EXPOSURE LIMITS (continued)
INGREDIENT VALUE UNIT TYPE AUTH SKIN*
-----------------------------------------------------------------------------
OSHA STANDARD 1910.1048
FORMALDEHYDE......................... 0.5 PPM TWA OSHA
OSHA ACTION LEVEL
* SKIN NOTATION: Listed substances indicated with 'Y' under SKIN refer to
the potential contribution to the overall exposure by the cutaneous route
including mucous membrane and eye, either by airborne or, more particularly,
by direct contact with the substance. Vehicles can alter skin absorption.
SOURCE OF EXPOSURE LIMIT DATA:
- 3M: 3M Recommended Exposure Guidelines
- ACGIH: American Conference of Governmental Industrial Hygienists
- CMRG: Chemical Manufacturer Recommended Exposure Guidelines
- OSHA: Occupational Safety and Health Administration
- NONE: None Established
-----------------------------------------------------------------------------
8. HEALTH HAZARD DATA
-----------------------------------------------------------------------------
EYE CONTACT:
Mild Eye Irritation: signs/symptoms can include redness, swelling,
pain, and tearing.
SKIN CONTACT:
Mild Skin Irritation: signs/symptoms can include redness, swelling,
and itching.
INHALATION:
Irritation (upper respiratory): signs/symptoms can include soreness
of the nose and throat, coughing and sneezing.
IF SWALLOWED:
Ingestion is not a likely route of exposure to this product.
Ingestion may cause:
Irritation of Gastrointestinal Tissues: signs/symptoms can
include pain, vomiting, abdominal tenderness, nausea, blood in
vomitus, and blood in feces.
-----------------------------------------------------------------------------
SECTION CHANGE DATES
-----------------------------------------------------------------------------
PRECAUTIONARY INFO. SECTION CHANGED SINCE November 02, 2000 ISSUE
-----------------------------------------------------------------------------
Abbreviations: N/D - Not Determined N/A - Not Applicable CA - Approximately
MSDS: 3M BRAND FIRE BARRIER CP-25 WB+ CAULK (REVISED)
May 21, 2001 PAGE 6
-----------------------------------------------------------------------------
The information in this Material Safety Data Sheet (MSDS) is believed to
be correct as of the date issued. 3M MAKES NO WARRANTIES, EXPRESSED OR
IMPLIED, INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR COURSE OF
PERFORMANCE OR USAGE OF TRADE. User is responsible for determining
whether the 3M product is fit for a particular purpose and suitable for
user's method of use or application. Given the variety of factors that
can affect the use and application of a 3M product, some of which are
uniquely within the user's knowledge and control, it is essential that
the user evaluate the 3M product to determine whether it is fit for a
particular purpose and suitable for user's method of use or application.
3M provides information in electronic form as a service to its customers.
Due to the remote possibility that electronic transfer may have resulted
in errors, omissions or alterations in this information, 3M makes no
representations as to its completeness or accuracy. In addition,
information obtained from a database may not be as current as the
information in the MSDS available directly from 3M.
PRODUCT DATA SHEET
Series AS200
Elastomeric Spray
Reproduced from Electronic Media
1. PRODUCT DESCRIPTION
FEATURES
SpecSeal?Elastomeric Spray Coating is a non-halogenated latex-based, highly
elastomeric coating designed to provide passive smoke and fire protection in
?Water-Based
construction joints.
for easy installation
SpecSeal?Elastomeric Spray Coating is engineered to adhere to virtually all
and cleanup.
construction surfaces and may be applied using airless spray equipment or
with a brush (for small applications or touch ups). ?Non-halogenated.
SpecSeal?Elastomeric Spray Coating dries to form a flexible shield against
?Thixotropic
the propagation of fire. Its premium latex binder system is totally resistant to
for high-build application.
water and will not re-emulsify after drying. SpecSeal?Elastomeric Spray Coating
contains no inorganic fibers, asbestos, solvents.
?Auto bonding.
2. APPLICATIONS
?Safe ... no solvents!
SpecSeal?Elastomeric Spray Coating is designed primarily for the protection
of construction joints and certain through-penetrations. No asbestos!
3. PHYSICAL PROPERTIES
?Flexible!
See Table A.
4. PERFORMANCE ?Water Resistant!
When applied to a wet film thickness of 1/8" (3.2mm) over appropriate backing
?Low Abrasion
materials, SpecSeal?Elastomeric Spray Coating has been successfully tested
for longer pump life
in one, two and three hour joints. Consult factory for individual system designs
and less maintenance.
and application requirements.
LIMITATIONS: Use product as per manufacturer's instructions. Use only in
?UL Classified.
applications per the manufacturer's tested and published designs or specific
recommendations. End user must ultimately determine the suitability of the ?Tested with
product and designs to his specific requirement and assumes responsibility for Direct-Applied
its use. PRODUCT CONTAINS WATER AND IS CONDUCTIVE UNTIL DRY.
Fireproofing.
DO NOT APPLY IN THE PRESENCE OF EXPOSED OR ENERGIZED
ELECTRICAL CONDUCTORS.
5. SPECIFICATIONS
The fire protective joint coating shall be a water-based, non-halogenated
elastomeric coating and shall contain no solvents, inorganic fibers, nor asbestos.
The coating shall dry to form a flexible, moisture resistant film and shall adhere
to all common construction surfaces. The coating shall be thixotropic and shall
be capable of being applied by brush, trowel or by airless spray. The approved
coating shall be SpecSeal?Elastomeric Spray.
SPECIFIED DIVISIONS
DIV. 7 07840 Through-Penetration Firestopping
FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY UNDERWRITERS
LABORATORIES INC. ? DIV. 13 13900 Special Construction Fire Suppression & Supervisory
FOR USE IN JOINT SYSTEMS &
Systems
THROUGH-PENETRATION
FIRESTOP SYSTEMS.
3L73
DIV. 15 15250 Mechanical Insulation ?Fire Protection
SEE UL FIRE RESISTANCE DIRECTORY
DIV. 16 16050 Basic Electrical Materials & Methods
FILL, VOID, OR CAVITY MATERIALS
CLASSIFIED BY UNDERWRITERS
LABORATORIES INC.
FOR USE IN JOINT SYSTEMS &
For the latest Product and System Information, Call
THROUGH-PENETRATION
FIRESTOP SYSTEMS.
STI'S FACTS-ON-DEMAND automated information attendant
SEE UL DIRECTORY OF PRODUCTS
CERTIFIED FOR CANADA AND
system by dialing toll-free (888)526-6800!
UL FIRE RESISTANCE DIRECTORY
Page 1 of 4 STI Product Data Sheet ?Series AS200 Elastomeric Spray FOD-5042 12/99
Table A: PHYSICAL PROPERTIES Fig. 1: METALLIC PIPE PENETRATIONS - CONCRETE/MASONRY FLOORS & WALLS
Color Pale Blue
Odor Mild Latex
Specific Gravity 1.1
Solids 75%
Flame Spread 0*
Smoke
Developed 25*
?8.75%**
Movement
Coverage 12.8 sq ft/gal @ 1/8
0.31 sq m/l @ 3.2mm
Viscosity 110,000 cps
pH 7.5
Solvent Content None UL System No. C-AJ-1318
120?F (49?C) F Rating ?2 Hr ?T Rating ?0 Hr
In-Service Temp.
Steel or Iron Pipe: <12", Copper Pipe: <6"
Drying Time Annulus: Point Contact to 2"
Tack Free 2 Hours Forming Material: Nom 4 pcf mineral wool to 4" depth
24-48 HoursA
Dry Through Spray Depth: 1/8" wet depth (+1/2" overlap)
* Tested to ASTM E84 (UL723) @ 14% coverage.
**500 Cycles per UL2079, AC30 (ICBO) and ASTM E1399
A
Dependent on temperature and humidity. Fig. 2: SLAB-EDGE SAFING GAP APPLICATIONS
6. INSTALLATION
INSTRUCTIONS
GENERAL: Areas to be protected
Framing
must be clean and free of oil, loose
Curtain
dirt, rust or scale. Recommended
Visions Wall
storage temperatures range
Panels Insulation
between 40癋 (4癈) and 95癋
(35癈). Recommended application
temperature range is 60癋 (16癈) to Framing
90癋 (32癈). When applying product
Covers
at the lower end of the temperature
range, warming the material to 70癋
Elastomeric
(21癈) will enhance drying
Spray
characteristics. Drying time will vary
Spandrel
according to prevailing temperature
Panels
and humidity. Allow to thoroughly dry
before exposure to moisture.
Consult appropriate manufacturer's
drawing for system design
requirements. Forming or packing
materials may be required as an
Mineral
integral part of various system
Wool
designs.
Coating may be applied by airless
spray in a single pass up to 3/16"
Concrete Floor
(4.8mm) wet coating depth. If
applying by brush or spraying on Assembly
vertical surfaces where coating
appears to be prone to slumping,
UL System No. CW-S-2003
multiple coats or the application of a Integrity Rating ?2 Hr
thin tack coat may be required. DO Insulation Rating ?1/2 Hr
Joint Width: Nom 8 in. wide.
NOT ATTEMPT TO THIN Forming Material: Nom 6 pcf mineral wool to 4" depth.
PRODUCT BY ADDING WATER. Spray Depth: 1/8" wet depth (+1/2" lap onto adjoining substrates)
Page 2 of 4 STI Product Data Sheet ?Series AS200 Elastomeric Spray FOD-5042 12/99
Fig. 3: FIREPROOFED STRUCTURAL PENETRATIONS - GYPSUM WALLBOARD WALLS
UL System No. HW-D-0099
Assembly Rating ?1 & 2 Hr
Movement Capabilities: ?8.75% Compress/Extend
Structural Support: Steel I Beam or Bar Joist protected with Spray-Applied Fire Resistive Materials.
Forming Material: Nom 6 pcf mineral wool to full depth.
Spray Depth: 1/8" wet depth (+2" lap onto fireproofing and 1/2" lap onto wall) on both sides.
Fig. 4: STEEL HVAC DUCT PENETRATIONS - Fig. 5: HEAD-OF-WALL JOINTS BETWEEN WALLS AND
GYPSUM WALLBOARD WALLS FIREPROOFED STEEL DECKS
UL System No. HW-D-0088
UL System No. W-L-7024
Assembly Rating ?1 & 2 Hr
F Rating ?1 & 2 Hr ?T Rating ?0 Hr
Movement Capabilities: ?8.75% Compress/Extend
Steel Duct: 20" by 12"
Nominal Joint Width: 1"
Forming Material: Nom 4 pcf mineral wool to 2" depth.
Forming Material: Nom 6 pcf mineral wool to full depth.
Spray Depth: 1/8" wet depth (+2" overlap onto duct, 1" lap onto wall) on both sides.
Spray Depth: 1/8" wet depth (+2" lap onto fireproofing and 1/2" lap onto wall) on both sides.
Steel Angles: No. 16 MSG steel angles.
Fig. 7: HEAD-OF-WALL JOINTS WITH FIREPROOFING
Fig. 6: STEEL HVAC DUCT PENETRATIONS -
INSTALLED INTO FLUTES AS FORMING
CONCRETE/MASONRY WALLS
UL System No. HW-D-0102
Assembly Rating ?1 & 2 Hr
UL System No. W-J-7006
Movement Capabilities: ?5% Compress/Extend ?Nominal Joint Width: 2"
F Rating ?2 Hr ?T Rating ?0 Hr
Forming Material: Spray-Applied Fire Resistive Materials
Steel Duct: 20" by 12"
to full depth allowing for a 2 in. relief gap between wallboard and fireproofing.
Forming Material: Nom 4 pcf mineral wool to 2" depth.
Relief gap packed with 4 pcf mineral wool insulation.
Spray Depth: 1/8" wet depth (+2" overlap onto duct, 1" lap onto wall) on both sides.
Spray Depth: 1/8" wet depth (+1/2" lap onto adjoining substrates) on both sides.
Steel Angles: No. 16 MSG steel angles.
Page 3 of 4 STI Product Data Sheet ?Series AS200 Elastomeric Spray FOD-5042 12/99
7. MAINTENANCE TABLE B: APPLICATION EQUIPMENT
INSPECTION: Installations should be
NOTICE: Spray application of SpecSeal Elastomeric Spray requires airless
inspected periodically for subsequent spray equipment meeting the following specifications:
damage. Following safety precautions
Working Pressure: Min. 3,000 PSI
listed below (See 9. Precautionary
Delivery: Min. 1.0 U.S. gpm (2.1 l/min.) recommended
Information) and pertinent installation Spray Tip Orifice: 0.023 to 0.026 recommended
guidelines, remove coating in Wetted Parts All seals and contact surfaces suitable for
damaged areas down to undamaged contact with latex emulsions.
material. Reapply fresh coating
The following airless spray equipment has demonstrated suitability for
material to original coating thickness. application of this product. STI makes no warranties concerning the suitability or
use of this equipment and has no affiliation of any kind with its manufacturer.
8. TECHNICAL SERVICE
Specified Technologies Inc. provides A minimum 3/8 fluid line is required, a 1/2 line is preferred. Consult pump
toll free technical support to assist in manufacturer for long hose runs or lifts to higher elevations. A reversible spray
product selection and installation tip is recommended. A 6 fan pattern is suggested to minimize overspray.
information.
The following equipment is manufactured by Titan Tool, Inc. Franklin Lakes, NJ:
9. PRECAUTIONARY
Item Item Name & Description
INFORMATION PowrTwin Model 3500 Sprayer Electric or gas powered airless sprayer
Consult Material Safety Data Sheet for
additional information on the safe
handling and disposal of this material. Table C: ORDERING INFORMATION
Wash areas of skin contact with soap
and water. Avoid contact with eyes. SpecSeal?Elastomeric Spray Coating is
available in 5 gal. pails, 55 gal. drums are
The use of an OSHA or NIOSH
available on a special order basis.
approved mask for dust and mist
AS205 5 gal. Pail 1,155 cu. in. (19 liters)
environment is recommended. Apply
in areas with adequate ventilation.
Additional SpecSeal Products...
CAUTION: COATING IS CONDUC- ES Series Sealant Inexpensive water-based Elastomeric Sealant for construction joint
applications. Design to provide up to ?25% movement.
TIVE UNTIL DRY. DO NOT APPLY
TO OR IN THE PRESENCE OF SSS Series Sealant The industry's most versatile sealant provides the firestopping solutions
for a wide range of combustible and noncombustible applications. Water-
ENERGIZED ELECTRICAL CON- based intumescent sealant expands up to 8X!
DUCTORS. INSTALL UNDER THE SSP Firestop Putty Available both in bar form and in pads, putty provides easy retrofit for
SUPERVISION OF PLANT OR through-penetrations and economical protection for electrical boxes.
Firestop Mortar Lightweight, versatile and economical! The best choice for large or
FACILITY ELECTRICAL ENGINEER
complex installations.
OR SAFETY MANAGER. Pensil?Silicones Sealants and foam for through-penetrations and construction joints.
Unexcelled aging characteristics and flexibility.
10. AVAILABILITY
Intumescent Wrap Strips Two grades of intumescent wrap strips provide an unmatched
SpecSeal?Elastomeric Spray combination of flexibility, economy, and expansion (up to 30X). Systems
Coating is available from authorized for plastic pipes including FR Polypropylene up to 8" trade size!
distributors. Consult factory for the Molded Firestop Collars Easy to install, economical protection for ABS and PVC pipes (both
solid and foam core) as well as CPVC, PVDF, and FRPP. Collars
names and locations of the nearest available up to 6" trade size.
sales representatives or distributors.
CITY OF NEW YORK MEA 310-99-M
Important Notice: All statements, technical information, and recommendations contained herein
Specified
are based upon testing believed to be reliable, but the accuracy and completeness thereof is not
guaranteed.
WARRANTY: Specified Technologies Inc. manufactures its goods in a manner to be free of defects.
Should any defect occur in its goods (within one year), Specified Technologies Inc., upon prompt
Technologies
notification, will at its option, exchange or repair the goods or refund the purchase price.
Limitations and Exclusions: THIS WARRANTY IS IN LIEU OF ALL OTHER
REPRESENTATIONS EXPRESSED OR IMPLIED (INCLUDING THE IMPLIED WARRANTIES OF
Inc.
MERCHANTABILITY OR FITNESS FOR USE) AND UNDER NO CIRCUMSTANCES SHALL
SPECIFIED TECHNOLOGIES INC. BE RESPONSIBLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL PROPERTY DAMAGE OR LOSSES. PRIOR TO USE, THE USER SHALL 200 Evans Way ?Somerville, NJ 08876
DETERMINE THE SUITABILITY OF THE PRODUCT FOR ITS INTENDED USE, AND THE USER
Phone: (800) 992-1180 ?Fax: (908) 526-9623
ASSUMES ALL RISKS AND LIABILITY FOR SUBSEQUENT USE.
Facts-On-Demand: (888) 526-6800
No statement or recommendation not contained herein shall have any force or effect unless in an
agreement signed by officers of seller and manufacturer.
STI on the WEB: www.stifirestop.com
MADE IN THE USA ?COPYRIGHT ?2000 SPECIFIED TECHNOLOGIES, INC.
Page 4 of 4 STI Product Data Sheet ?Series AS200 Elastomeric Spray FOD-5042 12/99
PRODUCT DATA SHEET
Series ES
Elastomeric Sealant
Reproduced from Electronic Media
1. PRODUCT DESCRIPTION FEATURES
SpecSeal?Elastomeric Sealant is a non-halogenated latex-based, highly
?Water-Based for easy
elastomeric caulk designed to provide passive smoke and fire protection in
installation and cleanup.
construction joints. This material is also designed to restore sound attenuation
properties to sound-rated ceilings and partitions.
?Non-halogenated.
SpecSeal?Elastomeric Sealant is engineered to adhere to virtually all
?Thixotropic for
construction surfaces and may be applied using standard caulking equipment
high-build application.
or by toweling. SpecSeal?Elastomeric Sealant dries to form a flexible shield
against the propagation of fire. Its premium latex binder system is totally ?Auto bonding.
resistant to water and will not re-emulsify after drying. SpecSeal?Elastomeric
?Safe... No solvents!
Sealant contains no inorganic fibers, asbestos, solvents.
No asbestos!
2. APPLICATIONS
?Elastomeric!
SpecSeal?Elastomeric Sealant is designed primarily for the protection of
construction joints. ?Water-Resistant!
3. PHYSICAL PROPERTIES
?UL Classified.
See Table A.
?Acoustical sealant!
4. PERFORMANCE
When applied to a wet film thickness of 1/4" (6.3 mm) to 1/2" (12.5 mm) over
appropriate backing materials, SpecSeal?Elastomeric Sealant has been FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY UNDERWRITERS
successfully tested in one, two, and three hour joints when tested in LABORATORIES INC. ?br>
accordance with UL2079 (ASTM E1966). All tested systems have been cycled FOR USE IN JOINT SYSTEMS.
500 times at total movement up to 50%. Consult factory for individual system SEE UL FIRE RESISTANCE DIRECTORY
3L73
designs and application requirements.
FILL, VOID, OR CAVITY MATERIALS
LIMITATIONS: Use product as per manufacturer's instructions. Use only in CLASSIFIED BY UNDERWRITERS
applications per the manufacturer's tested and published designs or per LABORATORIES INC.
FOR USE IN JOINT SYSTEMS.
specific recommendations. End user must ultimately determine the suitability SEE UL DIRECTORY OF PRODUCTS
CERTIFIED FOR CANADA AND
of the product and designs to his specific requirement and assumes UL FIRE RESISTANCE DIRECTORY
responsibility for its use.
Fig 2: RECOMMENDED JOINT DESIGNS - AVOIDING THREE-POINT ADHESION
Fig. 1: EXAMPLE OF MAINTAINING STC
VALUES OF WALL AND CREATING AN
EFFECTIVE SOUND BARRIER
In the example shown above, sealant is This example illustrates sealant applied
Arrows show path of sound travel.
applied (over foam backer rod) flush with to three planes. Bond breaker tape is
wall surface. Backer rod provides a applied to one surface to prevent three-
release surface allowing sealant to point adhesion, eliminating stress on joint
contract after drying to the recommended as sealant dries and enhancing movement
hour glass cross-sectional profile. capabilities.
For the latest Product and System Information, Call
STI'S FACTS-ON-DEMAND automated information attendant
Sealant reduces sound transmission by
system by dialing toll-free (888)526-6800!
blocking path of sound travel.
Page 1 of 4 STI Product Data Sheet ?Series ES Elastomeric Sealant FOD-5032 12/99
Fig. 3: HEAD-OF-WALL JOINT - GYPSUM WALLBOARD WALL TO
Table A: PHYSICAL PROPERTIES
CONCRETE FLOOR
Product Name Series ES
Elastomeric Sealant
Color Pale Blue
Odor Mild Latex
Density 10 Lb/Gal
Solids 66%
pH 7.5
120癋 (49癈)
In-Service Temp.
Flame Spread 5*
Smoke
Development 5*
?5%**
Movement
Solvent Content None
Drying Time
2 HoursA
Tack Free
5 to 7 DaysA
Dry Through
Acoustical ASTM C919
UL System No. HW-D-0079
* Tested to ASTM E84 (UL723) at 14% surface
Assembly Rating ?1 & 2 Hr ?Movement Capabilities: 25% Compress.
** 500 Cycles per UL2079, AC30 (ICBO) and
Nominal Joint Width: 3/4 ?Forming Material: In 1 hr walls, apply bond breaker tape to ceiling track.
ASTM E1399
Sealant Depth: 1/2 depth on both sides.
A
Dependent on temperature and humidity
5. SPECIFICATIONS Fig. 4: HEAD-OF-WALL JOINT - GYPSUM WALLBOARD WALL CUT
TO FIT CONTOURS OF STEEL DECK
Consult factory for recommended
specification.
6. INSTALLATION
INSTRUCTIONS
GENERAL: Areas to be protected
must be clean and free of oil, loose
dirt, rust or scale. Recommended
storage and application temperatures
range between 40癋 (4癈) and 95癋
(35癈). When applying product at
the lower end of the temperature
range, warming the material to 70癋
(21癈) will enhance drying
characteristics. Drying time will vary
according to prevailing temperature UL System No. HW-D-0103
Assembly Rating ?1 & 2 Hr ?Movement Capabilities: 25% Compress.
and humidity. Allow to thoroughly dry Nominal Joint Width: 3/4 ?Forming Material: In 1 hr walls, apply bond breaker tape to ceiling track.
before exposure to moisture. Sealant Depth: 1/2 depth on both sides.
Consult appropriate manufacturer's
Fig. 5: HEAD-OF-WALL JOINT - GYPSUM WALLBOARD WALL TO
drawing for system design
CONCRETE OVER STEEL DECK
requirements. Forming or packing
materials may be required as an
integral part of various system
designs. See Table B on Page 4 for
estimation information.
Sealant is auto-bonding and may be
applied in stages. DO NOT
ATTEMPT TO THIN PRODUCT BY
ADDING WATER.
THIS PRODUCT IS DESIGNED
FOR PROFESSIONAL INSTALLA-
TION ONLY. This sealant is designed
to contract while drying. Proper joint
design is critical to sealant perfor-
mance. Avoid three point adhesion UL System No. HW-D-0034
Assembly Rating ?1 & 2 Hr ?Movement Capabilities: ?5% Compress/Extend.
through the use of appropriate back- Nominal Joint Width: 1 ?Forming Material: Nom 4 pcf mineral wool to full depth.
ing or bond-breaking materials. Sealant Depth: 1/2 depth on both sides.
Page 2 of 4 STI Product Data Sheet ?Series ES Elastomeric Sealant FOD-5032 12/99
Fig. 6: HEAD-OF-WALL JOINT - MASONRY Fig. 7: HEAD-OF-WALL JOINT - MASONRY
WALL TO CONCRETE OVER STEEL DECK WALL TO CONCRETE FLOOR
UL System No. HW-D-0039 UL System No. HW-D-0041
Assembly Rating ?2 Hr Assembly Rating ?2 Hr
Movement Capabilities: ?5% Compress/Extend. Movement Capabilities: ?2.5% Compress/Extend or 25% Compress.
Nominal Joint Width: 1 Nominal Joint Width: 1 or 3/4 (See System).
Forming Material: Nom 4 pcf mineral wool to full depth. Forming Material: Optional foam backer rod.
Sealant Depth: 1/4 depth on both sides. Sealant Depth: 1 or 1/2 (See System) on both sides.
Fig. 8: FLOOR TO FLOOR JOINT - CONCRETE Fig. 9: FLOOR TO WALL JOINT - CONCRETE
FLOOR TO CONCRETE FLOOR FLOOR TO CONCRETE WALL
UL System No. FF-D-0005 UL System No. FW-D-0005
Assembly Rating ?2 Hr Assembly Rating ?2 Hr
Movement Capabilities: ?2.5% Compress/Extend Movement Capabilities: ?2.5% Compress/Extend
Nominal Joint Width: 1 Nominal Joint Width: 1
Forming Material: Optional foam backer rod. Forming Material: Optional foam backer rod.
Sealant Depth: 1 top and bottom. Sealant Depth: 1 top and bottom.
Fig. 10: FLOOR TO FLOOR JOINT - CONCRETE Fig. 11: FLOOR TO WALL JOINT - CONCRETE
FLOOR TO CONCRETE FLOOR FLOOR TO CONCRETE WALL
UL System No. FF-D-1008 UL System No. FW-D-1007
Assembly Rating ?3 Hr Assembly Rating ?3 Hr
Movement Capabilities: ?5% Compress/Extend Movement Capabilities: ?5% Compress/Extend
Nominal Joint Width: 4 Nominal Joint Width: 4
Forming Material: Nom 4 pcf mineral wool to 4 depth. Forming Material: Nom 4 pcf mineral wool to 4 depth.
Sealant Depth: 1/2 depth of sealant. Sealant Depth: 1/2 depth of sealant.
Page 3 of 4 STI Product Data Sheet ?Series ES Elastomeric Sealant FOD-5032 12/99
See Figure 2 for recommended joint Table B: PRODUCT ESTIMATION INFORMATION
designs. Consult ASTM C1193 (Construction Joints)
Standard Guide for Use of Joint JOINT PER 1/4" INSTALLED DEPTH PER 1/2" INSTALLED DEPTH PER 1" INSTALLED DEPTH
Sealants for additional guidelines WIDTH CU IN/FT FT/GAL GAL/100 FT CU IN/FT FT/GAL GAL/100 FT CU IN/FT FT/GAL GAL/100 FT
concerning the proper application of 0.5 1.5 154 .65 3 77.0 1.3 6 38.5 2.6
sealant materials. 0.75 2.3 102 .95 4.5 51.3 1.9 9 25.7 3.9
1.0 3.0 77 1.3 6.0 38.5 2.6 12 19.3 5.2
7. MAINTENANCE
1.5 4.5 51 2 9.0 25.7 3.9 18 12.8 7.8
Inspection: Installations should be 2.0 6.0 38 2.6 12 19.3 5.2 24 9.6 10.4
inspected periodically for subsequent 2.5 8.0 31 3.3 15 15.4 6.5 30 7.7 13.0
damage. Following safety precau- 3.0 9.0 25 3.9 18 12.8 7.8 36 6.4 15.6
tions listed below (See 9. 3.5 11 22 4.6 21 11.0 9.1 42 5.5 18.2
Precautionary Information) and per- 4.0 12 19 5.2 24 9.6 10.4 48 4.8 20.8
tinent installation guidelines, remove 5.0 15 15 6.5 30 7.7 13.0 60 3.9 26.0
coating in damaged areas down to
6.0 18 12 7.8 36 6.4 15.6 72 3.2 31.2
undamaged material. Reapply fresh
coating material to original coating
Table C: ORDERING INFORMATION
thickness.
SpecSeal?Elastomeric Sealant is
8. TECHNICAL SERVICE available in caulk tubes, sausages and pails.
Specified Technologies Inc. provides Cat. No. Description
ES100 10.3 oz. Tube (304 ml) 18 cu.in.
toll free technical support to assist in
ES129 29.0 oz. Tube (858 ml) 52 cu.in.
product selection and installation
ES120 20 oz. Sausage (592 ml) 36 cu. in.
information.
ES105 5 Gal. Pail (19.0 liters) 1,155 cu.in.
9. PRECAUTIONARY
INFORMATION Additional SpecSeal Products...
Series AS200 Spray Inexpensive water-based Elastomeric Spray Coating for construction
Consult Material Safety Data Sheet joint applications. Designed to provide up to ?8.75% movement.
for additional information on the safe Series SSS Sealant The industry's most versatile sealant provides the firestoppping
solutions for a wide range of combustible and noncombustible
handling and disposal of this material. applications. Water-based intumescent sealant expands up to 8x!
Wash areas of skin contact with soap SSP Firestop Putty Available both in bar form and in pads, putty provides easy retrofit for
and water. Avoid contact with eyes. through-penetrations and economical protection for electrical boxes.
Apply in areas with adequate SSB Firestop Pillows Durable, monolithic pillows for installations requiring quick and easy
retrofitting. Systems designed for pipes, cables and cable tray in all
ventilation. types of construction!
10. AVAILABILITY Firestop Mortar Lightweight, versatile and economical! The best choice for large or
complex installations.
SpecSeal?Elastomeric Sealant is Pensil?Silicones Sealants and foam for through-penetrations and construction joints.
Unexcelled aging characteristics and flexibility.
available from authorized distributors.
Intumescent Wrap Strips Two grades of intumescent wrap strips provide an unmatched
Consult factory for the names and combination of flexibility, economy, and expansion (up to 30x). Systems
locations of the nearest sales repre- for plastic pipes including FR Polypropylene up to 8" trade size!
sentatives or distributors. Packaging Molded Firestop Collars Easy to install, economical protection for ABS and PVC pipes (both
solid and foam core) as well as CPVC, PVDF, and FRPP. Collars
information and catalog numbers are available up to 6" trade size.
listed in Table C.
CITY OF NEW YORK MEA 290-98M
Important Notice: All statements, technical information, and recommendations contained herein
Specified
are based upon testing believed to be reliable, but the accuracy and completeness thereof is not
guaranteed.
WARRANTY: Specified Technologies Inc. manufactures its goods in a manner to be free of defects.
Should any defect occur in its goods (within one year), Specified Technologies Inc., upon prompt
Technologies
notification, will at its option, exchange or repair the goods or refund the purchase price.
Limitations and Exclusions: THIS WARRANTY IS IN LIEU OF ALL OTHER
REPRESENTATIONS EXPRESSED OR IMPLIED (INCLUDING THE IMPLIED WARRANTIES OF
Inc.
MERCHANTABILITY OR FITNESS FOR USE) AND UNDER NO CIRCUMSTANCES SHALL
SPECIFIED TECHNOLOGIES INC. BE RESPONSIBLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL PROPERTY DAMAGE OR LOSSES. PRIOR TO USE, THE USER SHALL 200 Evans Way ?Somerville, NJ 08876
DETERMINE THE SUITABILITY OF THE PRODUCT FOR ITS INTENDED USE, AND THE USER
Phone: (800) 992-1180 ?Fax: (908) 526-9623
ASSUMES ALL RISKS AND LIABILITY FOR SUBSEQUENT USE.
Facts-On-Demand: (888) 526-6800
No statement or recommendation not contained herein shall have any force or effect unless in an
agreement signed by officers of seller and manufacturer.
STI on the WEB: www.stifirestop.com
MADE IN THE USA ?COPYRIGHT ?2000 SPECIFIED TECHNOLOGIES, INC.
Page 4 of 4 STI Product Data Sheet ?Series ES Elastomeric Sealant FOD-5032 12/99
PRODUCT DATA SHEET
PEN200
Silicone Foam
Reproduced from Electronic Media
1. PRODUCT DESCRIPTION
Pensil?200 Firestop Foam (PEN200) is a two-component RTV silicone foam that features excellent crack-and-void filling capabilities. Unlike
other foams, PEN200 exhibits uniform cell structure, assuring reproducible, smoke-tight, fire resistant installations. Minimal pressure during
foaming virtually eliminates shrinkage of the cured material. The elastic properties of the foam readily accommodate minor vibration of the pipe,
conduit, etc. without loss of system integrity. Used in a 1:1 mix ratio, PEN200, when properly mixed, expands to approximately 4 times its original
volume, filling available spaces and forming an effective barrier against fire, smoke and water penetration.
2. APPLICATIONS
PEN200 has been tested as a seal for both floor and wall penetrations against the passage of fire, smoke or other hot gases. PEN200 is applied
in liquid form and then foams in place, readily sealing around penetrating items such as conduits, cables, duct work or mechanical piping.
PEN200 may also be useful in sealing areas such as control rooms against infiltration of airborne contaminants such as coal dust, dirt, etc. The
physical properties of PEN200 also make it an ideal product for use as a thermal or acoustical insulation, or for vibration dampening.
PEN200 is ideally suited for medium to large penetrations involving noncombustible penetrants, cable trays, or electrical, data, or telephone
cables.
3. PHYSICAL PROPERTIES
See Table A.
4. PERFORMANCE
PEN200 is the basis for systems that meet the exacting criteria of ASTM E814 (UL1479) as
well as to the time-temperature requirements of ASTM E119 (UL263). Systems have been
tested primarily for concrete or masonry construction with ratings up to 3 hours.
STI firestop systems are designed to maximize the fire resistance of the seal by not only sealing
off the spread of fire and hot gasses but also by minimizing the amount of heat conducted
through the assembly. Thus all systems have been designed to provide T Ratings capable of
matching the rating of the wall or floor assembly (where possible) when tested without penetrants.
6. INSTALLATION INSTRUCTIONS
GENERAL: Areas to be protected must be clean and free of oil, loose dirt, rust or scale.
Installation temperatures must be between 50癋 and 90癋.
PRIMING: Adhesion to concrete or masonry surfaces is generally very good. Bond breaking
contaminants must be removed using mechanical abrasion or solvent cleaning as required.
Adhesion to difficult substrates may be improved with the use of SS4155 primer.
SYSTEM SELECTION: Space limitations preclude highly detailed information pertaining to
individual application systems. Please consult the STI Product and Application Guide as well
as the UL?Fire Resistance Directory for additional information.
FORMING: PEN200 is installed as a liquid fill, therefore, forming or damming is required. In
some systems, forming materials may contribute to the fire-resistance rating of the system and FILL, VOID OR CAVITY MATERIALS
must be left in place. Consult appropriate STI drawing or UL Fire Resistance Directory for CLASSIFIED BY UNDERWRITERS
LABORATORIES INC. ?br>
system requirements.
FOR USE IN JOINTS SYSTEMS
MIXING & FOAMING: PEN200 is supplied as two equal components (Parts A & B). Settling (of
filler) and separation during storage is expected, therefore both components must be stirred SEE UL FIRE RESISTANCE DIRECTORY
with a clean paddle or suitable powered mixer prior to use.
FEATURES 5. SPECIFICATIONS
The firestopping product shall be a two-part, silicone, room temperature curing foam.
? High Resilience
The foam shall be completely water resistant and shall contain no solvents nor inorganic
allows movement due to
expansion, contraction, or fibers of any kind. The through-penetration firestop foam shall be UL Classified and/or
vibration. FM Systems Approved and tested to the requirements of ASTM E814 (UL1479).
SPECIFIED DIVISIONS
? Excellent Water
Resistance DIV. 7 07840 Through-Penetration Firestopping
for water-tight sealing.
DIV. 13 13900 Special Construction Fire Suppression & Supervisory
Systems
? Soft Setting Foam
for easy retrofitting of cables.
DIV. 15 15250 Mechanical Insulation ?Fire Protection
? Uniform Cell Structure DIV. 16 16050 Basic Electrical Materials & Methods
ensures reproducible results every
time. No charts to check!
For the latest Product and System Information, Call
? Excellent Adhesion
to most building substrates. STI'S FACTS-ON-DEMAND automated information attendant
system by dialing toll-free (888)526-6800!
? Excellent Smoke Seal
Page 1 of 2 STI Product Data Sheet ?PEN200 Silicone Foam FOD-5008 12/99
Table A: PHYSICAL PROPERTIES
After the A and B components have been individually stirred, mix equal parts of PEN200A
and PEN200B. Mixing may be accomplished using a paddle mixer or other suitable
As Supplied Part A Part B
power mixer in a container or by the use of automatic mixing and dispensing equipment.
(Base) (Curing Agent)
If paddle mixing is used, mix aggressively for 30 seconds immediately before transferring
Appearance Black Liquid Off-White Liquid
to the penetration. Product set will occur in 1-3/4 to 5 minutes at room temperature.
Mechanical mixing and dispensing is recommended for large volume applications. Specific Gravity 1.21 1.21
PEN200 when properly mixed, will expand to approximately four times its original Consistency Pourable Pourable
volume, to yield a foam density of 14-18 lbs./cu. ft. Installation of foam in confined
Viscosity 75 Poise 75 Poise
spaces will result in higher densities. Incomplete mixing of parts A and B will result in a
Storage Warranty
non-homogeneous product with a characteristic marbleized appearance. Measurement
Period* 6 Months 6 Months
of foam density provides the most accurate determination of proper mixing.
CURE RATE: Properly mixed components will set within 1-3/4 to 5 minutes at room Cured Properties Equal Parts A and B
1:1 Mix ratio as cured
temperature. Cure time is affected by the temperature of the mix. Lower temperatures
12 hours @ 77癋 (25癈)
will increase the cure time, while higher temperatures will decrease it. Optimum
temperatures for proper mixing and foaming are between 50癋 (10癈) & 90癋 (32癈). Work Life (after mix)** 100-300 Seconds
LIMITATIONS: Contact with materials containing sulfur or amine compounds may @77癋 (25癈)
retard or inhibit the cure of PEN200 Firestop Foam. Use with materials suspected to Appearance Black RTV Foam
contain these chemicals should be tested prior to installation.
Density 14-18 lb./cu.ft.
In areas where damage from rodents or other pests is a concern, protect foam seals
Yield Per 100 Lb Kit 5.5 to 7 cu. ft.
with a suitable wire screening.
(Parts A+B) (depending on density)
7. MAINTENANCE
Specific Gravity 0.29
Inspection: Installations should be inspected periodically for subsequent damage.
Any damage should be repaired using SpecSeal?products per the original approved Cellular Structure Approx. 50% Closed Cell
design. Oxygen Index 28 Minimum
Retrofit: When adding or removing penetrants, care should be taken to minimize Application
damage to the seal. Reseal using SpecSeal?products per the approved design. Temperature Range 50?90癋 (10?32癈)
NOTE: New penetrants of a different nature than the original design may require a
totally new firestop design or extensive modifications to the existing design. Reseal all
* From data of shipment stored in original unopened
openings as per the requirements of the modified design.
container @80癋(27癈).
8. TECHNICAL SERVICE
**Work life is the time during which the product remains
Specified Technologies Inc. provides toll free technical support to assist in product
pourable after mixing at 1:1 ratio.
selection and appropriate installation design. Design System Drawings suitable for
submittal or specification purposes are available on request.
9. PRECAUTIONARY INFORMATION
Table B: ORDERING INFORMATION
Consult Material Safety Data Sheet for additional information on the safe handling and
disposal of this material. Wash areas of skin contact with soap and water. Avoid
Cat. No. Description
contact with eyes. Containers of PEN200 A and B components must remain tightly
PEN200 Silicone Foam 100# Kit
closed prior to and after their use. PEN200 B CURING AGENT CAN GENERATE
(50# Part A, 50# Part B)
HYDROGEN GAS ON CONTACT WITH ACIDIC, BASIC OR OXIDIZING MATERIALS
AND SUCH CONTACT MUST BE AVOIDED.
WARNING: PEN200 generates hydrogen gas during the foaming process. Foaming
should be carried out in areas ventilated and monitored to insure that the lower explosive
limit of 4% of hydrogen in air is not exceeded. Hydrogen gas rises rapidly. Sources of
ignition at and above the work area should be extinguished.
10. AVAILABILITY
Pensil?Silicone Foam is available from authorized STI distributors. Consult factory
for the names and locations of the nearest sales representatives or distributors. The
standard package is a 100 lb. kit comprised of 50 lbs. Component "A" and 50 lbs.
Component "B".
Important Notice: All statements, technical information, and recommendations contained
herein are based upon testing believed to be reliable, but the accuracy and completeness
thereof is not guaranteed.
CITY OF NEW YORK MEA 12-93M
Important Notice: All statements, technical information, and recommendations contained herein
Specified
are based upon testing believed to be reliable, but the accuracy and completeness thereof is not
guaranteed.
WARRANTY: Specified Technologies Inc. manufactures its goods in a manner to be free of defects.
Should any defect occur in its goods (within one year), Specified Technologies Inc., upon prompt
Technologies
notification, will at its option, exchange or repair the goods or refund the purchase price.
Limitations and Exclusions: THIS WARRANTY IS IN LIEU OF ALL OTHER
REPRESENTATIONS EXPRESSED OR IMPLIED (INCLUDING THE IMPLIED WARRANTIES OF
Inc.
MERCHANTABILITY OR FITNESS FOR USE) AND UNDER NO CIRCUMSTANCES SHALL
SPECIFIED TECHNOLOGIES INC. BE RESPONSIBLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL PROPERTY DAMAGE OR LOSSES. PRIOR TO USE, THE USER SHALL 200 Evans Way ?Somerville, NJ 08876
DETERMINE THE SUITABILITY OF THE PRODUCT FOR ITS INTENDED USE, AND THE USER
Phone: (800) 992-1180 ?Fax: (908) 526-9623
ASSUMES ALL RISKS AND LIABILITY FOR SUBSEQUENT USE.
Facts-On-Demand: (888) 526-6800
No statement or recommendation not contained herein shall have any force or effect unless in an
agreement signed by officers of seller and manufacturer.
STI on the WEB: www.stifirestop.com
MADE IN THE USA ?COPYRIGHT ?2000 SPECIFIED TECHNOLOGIES, INC.
Page 2 of 2 STI Product Data Sheet ?PEN200 Silicone Foam FOD-5008 12/99
PRODUCT DATA SHEET
PEN300
Silicone Sealant
Reproduced from Electronic Media
1. PRODUCT DESCRIPTION
Pensil?Silicone Sealants are one-part neutral curing silicone sealants exhibiting
superior performance in applications where sealing apertures in walls and floors
are needed to control the spread of fire, smoke, toxic gasses, and water during fire
conditions.
Pensil Silicone Sealants react with atmospheric moisture to form a tough durable
seal that will adhere to most building substrates without the use of primers. Pensil
products do not contain asbestos or PCBs.
BASIC USES:
Pensil 300 Firestop Sealant is designed for use in Underwriters Laboratories (UL)
classified firestop systems. This material can also insulate openings to prevent
damage from occasional water spillage and dust penetration in sensitive areas.
Pensil 300 Firestop Sealant is available in non slump (PEN300) and self-leveling
(PEN300 SL) grades and may also be used to seal vertical and horizontal joints
between metals, masonry, concrete and other common construction materials.
Pensil 300 is especially designed for use in static or dynamic joints. The low modulus
characteristic minimizes strain on the substrate surface and the elastomeric quality
allows excellent recovery from extension and compression cycling.
2. APPLICATIONS
Pensil 300 is used to seal through-penetrations involving non-combustible
FILL, VOID OR CAVITY MATERIALS penetrants, electrical, data, or telephone cables, construction gaps, expansion
CLASSIFIED BY UNDERWRITERS
joints, curtain wall safing applications, and top-of-wall joints.
LABORATORIES INC. ?br>
FOR USE IN JOINT SYSTEMS &
THROUGH-PENETRATION 3. PHYSICAL PROPERTIES
3L73 FIRESTOP SYSTEMS.
31X5 See Table A.
SEE UL FIRE RESISTANCE DIRECTORY
4. PERFORMANCE
FILL, VOID, OR CAVITY MATERIALS
CLASSIFIED BY UNDERWRITERS Pensil Silicone Sealants are the basis for systems that meet the exacting criteria
LABORATORIES INC.
of ASTM E814, UL 1479, ASTM E1966 (UL 2079), ASTM 1399, as well as to the
FOR USE IN JOINT SYSTEMS &
THROUGH-PENETRATION
time-temperature requirements of ASTM E119 (UL 263). Pensil 300 Sealant is
FIRESTOP SYSTEMS.
SEE UL DIRECTORY OF PRODUCTS ASTM C920 compliant. Systems have been tested with ratings up to 4 hours.
FEATURES 5. SPECIFICATIONS
The firestopping sealant shall be a one-part, neutral curing silicone sealant.
? Low Modulus allows up to
The sealant shall be completely water resistant and shall contain neither solvents
?50% movement in joints.
nor inorganic fibers of any kind. The through-penetration firestop sealant shall
? Auto Bonding allows fresh
allow movement of +25% and shall be UL Classified and/or FM Systems
sealant to adhere to cured
Approved and tested to the requirements of ASTM E814 (UL1479). The firestop
sealant.
joint sealant shall allow movement up to ?50% and shall be UL Classified and
? Excellent Water
tested to the requirements of UL2079.
Resistance for water-tight
sealing. SPECIFIED DIVISIONS
? Ozone and UV Resistant DIV. 7 07840 Through-Penetration Firestopping
for excellent weather ability and
DIV. 13 13900 Special Construction Fire Suppression & Supervisory
long service life.
Systems
? Excellent Chemical
DIV. 15 15250 Mechanical Insulation ?Fire Protection
Resistance protects in
polluted or corrosive DIV. 16 16050 Basic Electrical Materials & Methods
atmospheres.
? Excellent Adhesion to
For the latest Product and System Information, Call
most building substrates.
STI'S FACTS-ON-DEMAND automated information attendant
? Excellent Smoke Seal
system by dialing toll-free (888)526-6800!
? Neutral Cure
Page 1 of 4 STI Product Data Sheet ?PEN300 Silicone Sealant FOD-5005 12/99
Fig. 1: METALLIC PIPE PENETRATIONS
Table A: PHYSICAL PROPERTIES
Color Concrete
Flame SpreadA 5
Smoke DevelopmentA 45
350癋
In Service Temp
Hardness ShoreA ASTM D2240 25
Tensile Strength ASTM D412 270
Peel Strength ASTM C794-80 55 ppi
Movement Capability
?50%
ASTM C719
?35%
AC30
Stress @ 50% Extension
1/2" x 1/2" Bead 35 lbs/in
Tooling Time (Minutes) 30
Tack Free Time (Hours), ASTM C619 5-9
Sag; Slump (NS Grade) ASTM C639 0.1"
Ozone & UV Resistance
(Weatherometer Twin Arc) Excellent
Storage Warranty Period ** 12 months UL SYSTEM C-AJ-1198
F Rating: 3 hr ?T Rating: 0 hr
A
ASTM E84 (UL723) @14% coverage
Steel or Iron Pipe: 24", Copper Pipe: 4"
** From date of shipment if stored in original
Annulus: Point Contact to 2 1/4" ?Sealant Depth: 1/2"
unopened container at 80癋 (27癈).
Forming Material: Nom 4 pcf Mineral Wool
500 Cycles as per UL2079, AC30 (ICBO), and
Tightly Packed to a 3" Depth.
ASTM E1399
6. INSTALLATION INSTRUCTIONS
THROUGH-PENETRATION FIRESTOPPING
reapply. Install sealant to required depth.
Pensil 300 Sealant is approved for a wet or frost covered surfaces. Forming:
Work sealant into all areas exercising
variety of through-penetration firestop Some installations may require forming
care to eliminate voids or seams. In
applications. Some typical installations as either an integral part of the system or
gypsum wall board penetrations, crown
have been illustrated here to assist in the as an option to facilitate installation. In
sealant a minimum of 1/4" from penetrant
selection of the proper installation systems where forming is required,
to wallboard surface at a point approx. 1/
method. Space limitations preclude mineral wool batting (4 lb./cu. ft. density)
2" or more from opening.
highly detailed information pertaining to is recommended for use in through-
individual application systems. Please penetrations. Where forming materials For applications involving cable bundles,
consult the STI referenced drawing, the are required, cut oversized to allow for spread cables sufficiently to ensure that
STI Product and Application Guide, as tight packing. Position forming material sealant completely envelops all cables
well as the UL Fire Resistance Directory as required for the proper depth of fill and totally fills all voids to the required
for additional information. material. depth.
PREPARATION: All surfaces to receive FILL MATERIAL: Pensil Sealants may SMOKE SEALING: Pensil Silicone
Pensil sealant must be sound, dry, frost- be installed by caulking using a standard Sealants make an excellent smoke seal.
free, and free of bond-breaking caulking gun or from bulk containers Apply at gaps and seams to prevent the
contaminants and loose material. Wire using a bulk loading caulk gun, or by passage of smoke. Some SpecSeal
brush contact surfaces or wipe with a manually toweling using a mason's trowel Firestop Collar designs utilize Pensil
suitable solvent as necessary to remove or putty knife. If the sealant tends to pull Silicone Sealant as the smoke seal.
Consult the STI Product and Application
any contaminants. Mask all areas where back from a surface, clean the surface
Guide for further information.
adhesion is undesirable. Do not apply to using the methods described above and
Fig. 2: MISCELLANEOUS METALLIC PIPE & CABLE PENETRATIONS
UL SYSTEM W-L-1033 UL SYSTEM C-AJ-3023
F Rating: 2 hr ?T Rating: 0 F Rating: 3 hr ?T Rating: 1/2 hr
Steel Pipe: 6", Copper Pipe or Tubing: 4" Electrical, Telephone, or Data Cables
Sealant Depth: 1/4" (within annulus) + 3/8" Crown Annulus: 1/2" to 1" ?Sealant Depth: 1/2"
Forming Material: Nom 4 pcf Mineral Wool Forming Material: Nom 4 pcf Mineral Wool
Tightly Packed to a 1" Depth. Tightly Packed to a 4" Depth.
Page 2 of 4 STI Product Data Sheet ?PEN300 Silicone Sealant FOD-5005 12/99
Table B: SEALANT REQUIREMENTS IN CUBIC INCHES PER HALF INCH OF INSTALLED DEPTH
Pipe Size Size of Hole (Inches)
1-1/2 2 3 4 5 6 7 8 10 12 14 26
Trade Size Pipe O.D.
IMPORTANT NOTE: This table is for estimation purposes only.
1/2" 0.840 1.22 1.29 3.26 6.01
Consult UL Fire Resistance Directory or STI Product & Application
1" 1.313 0.42 0.89 2.86 5.61 9.14
Guide for specific installation requirements and limitations.
1-1/2" 1.900 2.12 4.87 8.40
2" 2.375 1.32 4.07 7.60 11.92
2-1/2" 2.875 3.04 6.57 10.89
3" 3.500 1.47 5.01 9.33 14.43 20.32
3-1/2" 4.000 3.53 7.85 12.96 18.85
4" 4.500 1.87 6.19 11.29 17.18 31.32 48.60
6" 5.563 1.98 7.09 12.98 22.03 39.31
8" 8.653 10.06 27.34
10" 10.750 11.75 63.20
12" 12.750 26.30
24" 24.000 76.60
CONSTRUCTION JOINTS
Pensil 300 Sealants are approved for midpoint at the time of sealant a sound, clean surface for sealant
sealing a variety of construction joint installation. For example, if Pensil 300 application. Dust, loose particles, etc.
applications. FIG. 3 illustrates some is to be installed in an expansion joint should be blown out of the joint with oil-
and movement is expected to be ?/8"
common joint designs in masonry free compressed air or vacuum cleaned.
construction. Space limitations preclude and the joint is not at its midpoint, the PRIMING: Pensil Silicone Sealants have
highly detailed information pertaining to joint width should be 3/4" plus any primer less adhesion to many
individual application systems. Please deviation from the joint midpoint. construction materials including
consult the STI referenced drawing, the Lap shear joints should have a bead untreated or uncoated concrete. Jobsite
STI Product and Application Guide, as width that is equal to, or greater than, trial applications are recommended if
well as the UL?Fire Resistance the total anticipated movement. contact surfaces are in any way
Directory for additional information. questionable. Application of SCP3154
IMPORTANT NOTE: Joint designs
JOINT DESIGNS: Joints firestopped with primer may remedy adhesion difficulties
incorporating Pensil?Silicone Sealants
Pensil 300 will accommodate ?0% for questionable concrete surfaces.
are not designed to be load bearing or
movement providing the joint is 1/2" or exposed to traffic. Joint seals must be MASKING: The use of masking tape is
wider. If the joint is less than 1/2" wide, protected by suitable metallic cover recommended where appropriate to
the movement should be limited to ?5% plates in exposed floor areas. insure a neat job and to protect adjoining
of the actual joint width. surfaces. Do not allow masking tape to
PREPARATORY WORK: Clean all
The dimensions of curtain wall touch clean surfaces to which the
concrete, masonry and stone joints of
expansion joints and similar applications silicone sealant is to adhere. Masking
all contaminants and impurities.
change daily as a result of solar heat tape should be removed immediately
Concrete laitance, all old sealants and
gain, positive and negative buffeting after the finish tooling of the Pensil
other surface treatments and protective
from wind forces, and throughout the Firestop Sealant.
coatings are examples of materials that
year because of seasonal changes. must be removed from the joint surfaces FORMING: Some installations may
If the firestop cannot be installed when to obtain proper sealant adhesion. require forming as either an integral part
the joint is at its midpoint of dimensional Porous substrates should be cleaned of the system or as an option to facilitate
extremes, the joint width should be where necessary by grinding, saw installation. In systems where forming
designed at twice the anticipated cutting, blast cleaning (sand or water), is required, mineral wool batting (4 lb./
movement, plus the dimensional mechanical abrading or a combination cu. ft. density), or other approved backer
amount the joint deviates from the of these methods are required to provide materials are recommended.
Fig. 3: TYPICAL JOINT INSTALLATION METHODS
Symmetrical Wall Installation Symmetrical Wall Installation Asymmetrical Wall Installation* Floor Joint Installation*
*Rated one side only.
Page 3 of 4 STI Product Data Sheet ?PEN300 Silicone Sealant FOD-5005 12/99
To calculate the volume of packing material 10. AVAILABILITY
required for the joint, add 20 - 25% to the Pensil?Silicone Sealants are available from authorized STI distributors. Consult factory
volume required for the joint at its greatest for the names and locations of the nearest sales representatives or distributors. Available
extension (for dynamic joints) or widest width packages and additional SpecSeal?Products are listed in Table D.
(for static joints). Where required, cut
Table C: PRODUCT ESTIMATION INFORMATION (Construction Joints)
forming material oversize to allow for tight
packing. Recess forming materials as JOINT PER 1/2" INSTALLED DEPTH PER 1" INSTALLED DEPTH PER 1-1/2" INSTALLED DEPTH
required for application of the proper depth WIDTH CU IN/FT FT/GAL GAL/100 FT CU IN/FT FT/GAL GAL/100 FT CU IN/FT FT/GAL GAL/100 FT
of fill material. 0.5 3.0 77.0 1.3 6 38.5 2.6 9 25.7 3.9
FILL MATERIAL: Apply Pensil 300 Firestop .75 4.5 51.3 1.9 9 25.7 3.9 13 17.1 5.8
Sealant in a continuous operation, 1.0 6.0 38.5 2.6 12 19.3 5.2 18 12.8 7.8
horizontally in one direction and vertically 1.5 9.0 25.7 3.9 18 12.8 7.8 27 8.6 11.7
from the bottom to the top of the joint 2.0 12 19.3 5.2 24 9.6 10.4 36 6.4 15.6
opening. A positive pressure adequate to 2.5 15 15.4 6.5 30 7.7 13.0 45 5.1 19.5
properly fill and seal the joint width should 3.0 18 12.8 7.8 36 6.4 15.6 54 4.3 23.4
3.5 21 11.0 9.1 42 5.5 18.2 63 3.7 27.3
be employed. Tool or strike Pensil Firestop
4.0 24 9.6 10.4 48 4.8 20.8 72 3.2 31.2
Sealant with light pressure to spread the
5.0 30 7.7 13.0 60 3.9 26.0 90 2.6 39.0
material against the backup material and the
6.0 36 6.4 15.6 72 3.2 31.2 108.0 2.1 46.8
joint surface. The lightweight consistency of
Pensil 300 Firestop Sealant responds easily
to light tooling pressure and facilitates void
free placement. On porous surfaces the Table D: ORDERING INFORMATION
excess sealant should be allowed to
progress through the initial cure or setup. It Cat. No. Description
should then be removed by abrasion or other
PEN300 10.5 oz Tube (304 ml) 18.3 cu. in.
mechanical means.
PEN305 5 Gal. Pail (19.0 liters) 1,155 cu. in.
7. MAINTENANCE
PEN305SL Self-Leveling 5 Gal. Pail (19.0 liters) 1,155 cu. in.
Inspection: Installations should be inspected
periodically for subsequent damage. Any
damage should be repaired using Additional SpecSeal Products...
SpecSeal?products per the original SSS Series Sealant The industry's most versatile sealant provides the firestoppping
solutions for a wide range of combustible and noncombustible
approved design. Cut away damaged
applications. Water-based intumescent sealant expands up to 8x!
material and reapply sealant as required.
LC Series Sealant An economical latex firestop sealant for noncombustible
8. TECHNICAL SERVICE applications. Non-halogenated, easy clean up, flexible, water-
Specified Technologies Inc. provides toll free resistant!
technical support to assist in product SSP Firestop Putty Available both in bar form and in pads, putty provides easy retrofit
selection and appropriate installation design. for through-penetrations and economical protection for electrical
boxes.
Design System Drawings suitable for
submittal or specification purposes are SSB Firestop Pillows Durable, monolithic pillows for installations requiring quick and easy
retrofitting. Systems designed for pipes, cables and cable tray in
available on request.
all types of construction!
9. PRECAUTIONARY INFORMATION Firestop Mortar Lightweight, versatile and economical! The best choice for large
Avoid contact with eyes. Uncured product or complex installations.
may irritate eyes on contact. Use only in well Intumescent Wrap Strips Two grades of intumescent wrap strips provide an unmatched
ventilated areas. To clean areas of skin combination of flexibility, economy, and expansion (up to 30X).
contact, wipe off uncured material with a dry Systems for plastic pipes including FR Polypropylene up to 8" trade
size!
cloth or paper towel prior to washing.
Waterless hand cleaners are particularly Elastomeric Joint Seals New economical products for sealing construction joints. Choose
caulk or spray applied products tested to UL2079.
effective while sealant is uncured. Consult
Material Safety Data Sheet for additional Molded Firestop Collars Easy to install, economical protection for ABS and PVC pipes (both
solid and foam core) as well as CPVC, PVDF, and FRPP. Collars
information on the safe handling and
available up to 6" trade size.
disposal of this material.
CITY OF NEW YORK MEA 12-93M
Important Notice: All statements, technical information, and recommendations contained herein
Specified
are based upon testing believed to be reliable, but the accuracy and completeness thereof is not
guaranteed.
WARRANTY: Specified Technologies Inc. manufactures its goods in a manner to be free of defects.
Should any defect occur in its goods (within one year), Specified Technologies Inc., upon prompt
Technologies
notification, will at its option, exchange or repair the goods or refund the purchase price.
Limitations and Exclusions: THIS WARRANTY IS IN LIEU OF ALL OTHER
REPRESENTATIONS EXPRESSED OR IMPLIED (INCLUDING THE IMPLIED WARRANTIES OF
Inc.
MERCHANTABILITY OR FITNESS FOR USE) AND UNDER NO CIRCUMSTANCES SHALL
SPECIFIED TECHNOLOGIES INC. BE RESPONSIBLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL PROPERTY DAMAGE OR LOSSES. PRIOR TO USE, THE USER SHALL 200 Evans Way ?Somerville, NJ 08876
DETERMINE THE SUITABILITY OF THE PRODUCT FOR ITS INTENDED USE, AND THE USER
Phone: (800) 992-1180 ?Fax: (908) 526-9623
ASSUMES ALL RISKS AND LIABILITY FOR SUBSEQUENT USE.
Facts-On-Demand: (888) 526-6800
No statement or recommendation not contained herein shall have any force or effect unless in an
agreement signed by officers of seller and manufacturer.
STI on the WEB: www.stifirestop.com
MADE IN THE USA ?COPYRIGHT ?2000 SPECIFIED TECHNOLOGIES, INC.
Page 4 of 4 STI Product Data Sheet ?PEN300 Silicone Sealant FOD-5005 12/99
PRODUCT DATA SHEET
Series SSS
Sealant
Reproduced from Electronic Media
1. PRODUCT DESCRIPTION Table A: APPLICATIONS
SpecSeal?Series SSS Sealant is a latex based, high solids firestop compound.
This material, when properly installed, will effectively seal penetration openings ? Metallic Pipes including steel,
against the spread of fire, smoke, toxic gasses and water. iron, or copper pipe and tubing
through all common constructions.
SpecSeal?Series SSS Sealant features STI's patented and proprietary two-
? Nonmetallic Pipes, Conduits
stage intumescent technology. When exposed to high temperatures or fire, this
& Tubing including PVC, CPVC,
material expands aggressively in a highly directionalized fashion to quickly close PVDF, PEX, PEX-AL-PEX, ABS, PB
off voids left by the burning or melting of combustible materials. through all common constructions.
SpecSeal?Series SSS Sealant's unique multi-viscosity formula yields a single ? Cable, Cable Trays & Bus
Duct
grade that has excellent caulking properties as well as high build properties on
vertical or overhead surfaces. This single grade may be pumped, caulked (standard ? HVAC Ductwork
cartridge or bulk loaded), knifed or troweled. In addition, SpecSeal?SSS does
? Insulated Pipes
not contain PCB's or asbestos.
? Multi-Service Penetrations
SpecSeal?Series SSS Sealant is FILL, VOID OR CAVITY MATERIALS including AC line sets, electrical,
CLASSIFIED BY UNDERWRITERS
storage stable (when stored telephone, or TV service entrance
LABORATORIES INC. ?FOR USE IN
and interior penetrations.
according to the manufacturer's THROUGH-PENETRATION
FIRESTOP SYSTEMS.
recommendations) and will not ? Complete Wood Floor
3L73
separate nor shrink when dried. SEE UL FIRE RESISTANCE DIRECTORY firestopping package for electrical,
plumbing, HVAC, TV and telephone.
SpecSeal?Series SSS Sealant will CLASSIFIED FILL, VOID, OR CAVITY
adhere to all common construction MATERIALS FOR USE IN THROUGH-
? Over 200 UL Classified
PENETRATION FIRESTOP SYSTEMS.
and penetrant materials and contains Systems utilizing this product as
SEE UL DIRECTORY OF PRODUCTS
the primary or secondary product.
CERTIFIED FOR CANADA AND
no solvents that might adversely UL FIRE RESISTANCE DIRECTORY
effect plastic pipes or cable jackets.
FEATURES 5. SPECIFICATIONS
The firestopping sealant shall be a one-part, two-stage intumescent latex
? Water-Based for easy installation,
compound. The sealant when exposed to high heat or flame shall be capable
cleanup, and disposal.
of expanding a minimum of 8 times. Range of continuing expansion shall be
? Two-Stage Intumescence
features extremely fast and from 230癋 to >1,000癋. The sealant shall be thixotropic and shall be capable
directionalized expansion. of caulking or troweling onto vertical surfaces or overhead. The sealant shall
? Endothermic Fillers be UL Classified and/or FM Systems Approved and tested to the requirements
absorb heat & release water.
of ASTM E814 (UL1479).
? High Solids Formula
means no shrinkage! SPECIFIED DIVISIONS
? Sandable & Paintable DIV. 7 07840 Through-Penetration Firestopping
(when dry)
DIV. 13 13900 Special Construction Fire Suppression & Supervisory
? Water-Resistant:
Will not re-emulsify when dry! Systems
? Safe for contact with plastics.
DIV. 15 15250 Mechanical Insulation ?Fire Protection
? Red Color for easy identification
and inspection. DIV. 16 16050 Basic Electrical Materials & Methods
? Multi Viscosity Grade means
excellent caulking properties along
with high build capabilities. For the latest Product and System Information, Call
? Excellent Smoke Seal
STI'S FACTS-ON-DEMAND automated information attendant
? Low VOC: Safe, No Solvents,
system by dialing toll-free (888)526-6800!
Non-Halogenated
Page 1 of 4 STI Product Data Sheet ?Series SSS Sealant FOD-5001 12/99
Table B: PHYSICAL PROPERTIES Shown below and on the following page are just a few of the most common
applications for SpecSeal Series SSS Sealant. Consult the STI Product &
Product Name Series SSS Sealant
Color Red Application Guide for over 200 available designs utilizing this product.
Odor Mild Latex
Density 9.4 Lb/Gal
80% ?2%
Solids
Fig. 1: METALLIC PIPE PENETRATIONS -
pH 8.3
CONCRETE/MASONRY FLOORS & WALLS
Expansion Begins 230癋 (110癈) 1st Stage
350癋 (177癈) 2nd Stage
Expansion Range 230癋 to >1,000癋
(110癈 to > 538癈)
Volume Expansion > 500% Free Expansion
130癋
In-Service Temp.
Flame Spread 0*
Smoke Development 10*
* Tested to ASTM E84 (UL723) at 14% surface
coverage (modified test for sealants and caulks).
2. APPLICATIONS
See Table A for a summary application list.
Series SSS Sealant is used to seal
through-penetrations as well as
UL SYSTEM C-AJ-1079 UL SYSTEM C-AJ-1217
construction gaps, blank openings and F Rating: 4 hr ?T Rating: 0 F Rating: 3 hr ?T Rating: 0
Steel or Iron Pipe: 24", Copper Pipe 6" Steel or Iron Pipe: 8", Copper Pipe 4"
joints. Series SSS has been tested for use
Annulus: Point Contact to 4" ?Sealant Depth: 1/2" Annulus: Point Contact to 1-1/4" ?Sealant Depth: 1/2"
with metallic penetrants up to 24" trade Forming Material: Nom 4 pcf Mineral Wool Forming Material: Nom 4 pcf Mineral Wool
Thickness: 1-1/2" for 6" Steel or Iron Pipe
size. This product is also used with other Tightly Packed to a 3" Depth.
3" for 4" Copper or 6" Iron or Steel Pipe
SpecSeal?Products such as SpecSeal?br>
Firestop Collars and Wrap Strips.
Fig. 2: INSULATED METALLIC PIPE PENETRATIONS -
3. PHYSICAL PROPERTIES CONCRETE/MASONRY FLOORS & WALLS
See Table B.
4. PERFORMANCE
SpecSeal?Series SSS Sealant is the
basis for systems that meet the exacting
criteria of ASTM E814 (UL1479) as well
as to the time-temperature requirements
of ASTM E119 (UL263). Systems have
been tested for all common forms of
construction and most common
penetrants with ratings up to 4 hours.
STI firestop systems are designed to
maximize the fire resistance of the seal
UL SYSTEM C-AJ-5087
by not only sealing off the spread of fire F Rating: 2 hr ?T Rating: 1
Steel or Iron Pipe: 12"
and hot gasses but also by minimizing
Insulated with 2" Thick Fiber Glass or Mineral Wool Pipe Insulation
the amount of heat conducted through Annulus: 1/2" to 1-1/2" ?Sealant Depth: 1/2"
Forming Material: Nom 4 pcf Mineral Wool Tightly Packed to a 3" Depth.
the assembly.
Table C: SEALANT REQUIREMENTS IN CUBIC INCHES PER HALF INCH OF INSTALLED DEPTH
Pipe Size Size of Hole (Inches)
1-1/2 2 3 4 5 6 7 8 10 12 14 26
Trade Size Pipe O.D.
IMPORTANT NOTE: This table is for estimation purposes only.
1/2" 0.840 1.22 1.29 3.26 6.01
Consult UL Fire Resistance Directory or STI Product & Application
1" 1.313 0.42 0.89 2.86 5.61 9.14
Guide for specific installation requirements and limitations.
1-1/2" 1.900 2.12 4.87 8.40
2" 2.375 1.32 4.07 7.60 11.92
2-1/2" 2.875 3.04 6.57 10.89
3" 3.500 1.47 5.01 9.33 14.43 20.32
3-1/2" 4.000 3.53 7.85 12.96 18.85
4" 4.500 1.87 6.19 11.29 17.18 31.32 48.60
6" 5.563 1.98 7.09 12.98 22.03 39.31
8" 8.653 10.06 27.34
10" 10.750 11.75 63.20
12" 12.750 26.30
24" 24.000 76.60
Page 2 of 4 STI Product Data Sheet ?Series SSS Sealant FOD-5001 12/99
Fig. 3: ELECTRICAL, DATA OR COMMUNICATIONS PENETRATIONS -
Thus all systems have been designed to
RATED GYPSUM WALLBOARD ASSEMBLIES
provide T Ratings capable of matching the
rating of the wall or floor assembly (where
possible) when tested without penetrants.
5. SPECIFICATIONS
See page 1.
6. INSTALLATION
INSTRUCTIONS
GENERAL: Areas to be protected must
be clean and free of oil, loose dirt, rust or
scale. Installation temperatures must be
between 35癋 and 100癋. Allow product
to dry a minimum of 24 hours before
UL SYSTEM W-L-3076 UL SYSTEM W-L-2093
exposure to moisture.
F Rating: 1 or 2 hr ?T Rating: 0 hr F Rating: 1 or 2 hr ?T Rating: 1, 1-1/2 hr
2" Rigid PVC, ENMT,
SYSTEM SELECTION: Selection of an Up to 4" Cable Bundle
Centered in 5" Opening or Optical Fiber Raceway.
appropriate firestop system design is 1-1/4" PVDF Optical Fiber Raceway.
Sealant Depth: 5/8" with 1/4" Crown
critical to the fire protection process. Space Sealant Depth: 5/8" with 1/4" Crown
limitations preclude highly detailed
information pertaining to individual Fig. 4: ELECTRICAL PENETRATIONS -
application systems. Please consult the CONCRETE/MASONRY FLOORS & WALLS
STI Product & Application Guide as well
as the UL?Fire Resistance Directory for
additional information.
FORMING: Some installations may
require forming as either an integral part
of the system or as an option to facilitate
installation. In systems where forming is
required, mineral wool batts (1-1/2" to 3"
nominal thickness, 4 lb./cu. ft. density) are
recommended. Some gypsum wallboard
systems utilize fiberglass. Cut forming
material over-size to allow for tight packing. UL SYSTEM C-AJ-3154 UL SYSTEM C-AJ-6008
Position forming material to allow for the F Rating: 3 hr ?T Rating: 1/2 hr F Rating: 3 hr ?T Rating: 0 hr
Aluminum or Copper Bus Duct 5,000 Amp
Electrical, Telephone or Data Cables
proper depth of fill material. Annulus: 0" to 2" Steel Cover Plate
Sealant Depth: 1/2" Sealant Depth: 1/2"
FILL MATERIAL: SpecSeal?Series SSS
Forming Materials: Nom 4 pcf Mineral Wool to 3" depth Forming Materials: Nom 4 pcf Mineral Wool
Sealant may be installed by caulking Tightly Packed to a depth of 1-1/2"
using a standard caulking gun or from
Fig. 5: BARE & INSULATED METALLIC PIPE PENETRATIONS - RATED GYPSUM WALLBOARD ASSEMBLIES
UL SYSTEM W-L-1049 UL SYSTEM W-L-5014 & W-L-5054 UL SYSTEM W-L-5051
F Rating: 2 hr ?T Rating: 0 hr F Rating: 1 & 2 hr ?T Rating: 1 & 2 hr F Rating: 1 & 2 hr ?T Rating: 1 & 2 hr
Steel or Iron Pipe: 24", Copper Pipe: 6" Steel or Iron Pipe: 12", Copper Pipe: 4" Steel, Iron, or Copper Pipe: 4", Insulated with 2"
Insulated with 2" Thick Fiber Glass
Annulus: Point Contact to 1-3/4" Foam Glass Pipe Insulation ?12" Wide 0.010" Thick
Sealant Depth: 5/8" with 1/4" Crown or Mineral Wool Pipe Insulation Metal Jacket Wrapped Around Insulation and Secured
Annulus: 1/2" to 1-1/2" with Metal Banding as Shown ?Annulus: 1/2" to 1-1/2"
Sealant Depth: 5/8" with 1/4" Crown Sealant Depth: 5/8" with 1/4" Crown
Page 3 of 4 STI Product Data Sheet ?Series SSS Sealant FOD-5001 12/99
bulk containers using a bulk loading caulk 8. TECHNICAL SERVICE
gun, or by manually troweling using a Specified Technologies Inc. provides toll free technical support to assist in product
mason's trowel or putty knife. If the selection and appropriate installation design. Design System Drawings suitable for
sealant tends to pull back from a surface, submittal or specification purposes are available on request.
clean the surface with a damp rag or
9. PRECAUTIONARY INFORMATION
sponge and reapply. Work sealant into
Consult Material Safety Data Sheet for additional information on the safe handling
all areas exercising care to eliminate
voids or seams. The surface of the and disposal of this material. Wash areas of skin contact with soap and water. Avoid
sealant can be smoothed using a putty contact with eyes. SEALANT IS CONDUCTIVE UNTIL DRY.
knife dipped in water. Adding water to
10. AVAILABILITY
the sealant itself is not recommended.
SpecSeal?Series SSS Sealant is available from authorized STI distributors. Consult
Sealant (when dry) may be sanded and
factory for the names and locations of the nearest sales representatives or distributors.
painted using most non-solvent based
Available packages and additional SpecSeal?Products are listed below.
paints. In gypsum wallboard
penetrations, crown sealant 1/4" from
penetrant to wallboard surface at a point Table D: ORDERING INFORMATION
approximately 1/2" or more from opening.
SMOKE SEALING: In some applications Cat. No. Description
including firestop collars, SpecSeal? SSS100 10.5 oz. Tube (311 ml) 19 cu.in.
Series SSS Sealant is recommended as SSS129 29 oz. Tube (858 ml) 52 cu. in.
a smoke seal. It is suggested in these SSS120 20 oz. Sausage (592 ml) 36 cu. in.
application that the sealant be applied to SSS102 2 Gal. Pail (7.6 liters) 462 cu.in.
both sides of walls. In floor applications, SSS105 5 Gal. Pail (19.0 liters) 1,155 cu.in.
a sealing bead is suggested top and
bottom.
Additional SpecSeal Products...
COVER PLATE: In some designs a
Series LC Sealant An economical latex firestop sealant for noncombustible appli-
galvanized steel cover plate (26 gauge)
cations. Non-halogenated, easy clean up, flexible,
may be used to upgrade the fire water-resistant!
resistance rating to 4 hours. Consult STI
SSP Firestop Putty Available both in bar form and in pads, putty provides easy
Product and Application Guide for
retrofit for through-penetrations and economical protection for
dimensional and fastening requirements.
electrical boxes.
7. MAINTENANCE SSB Firestop Pillows Durable, monolithic pillows for installations requiring quick and
INSPECTION: Installations should be easy retrofitting. Systems designed for pipes, cables and cable
inspected periodically for subsequent tray in all types of construction!
damage. Any damage should be Firestop Mortar Lightweight, versatile and economical! The best choice for large
repaired using SpecSeal?products per or complex installations.
the original approved design.
Pensil?Silicones Sealants and foam for through-penetrations and construction
RETROFIT: When adding or removing joints. Unexcelled aging characteristics and flexibility.
penetrants, care should be taken to Intumescent Wrap Strips Two grades of intumescent wrap strips provide an unmatched
minimize damage to the seal. Reseal combination of flexibility, economy, and expansion (up to 30X).
using SpecSeal?products per the Systems for plastic pipes including FR Polypropylene up to 8"
approved design. NOTE: New trade size!
penetrants of a different nature than the Molded Firestop Collars Easy to install, economical protection for ABS and PVC pipes
original design may require a totally new (both solid and foam core) as well as CPVC, PVDF, and FRPP.
firestop design or extensive modifications Collars available up to 6" trade size.
to the existing design. Reseal all Elastomeric Joint Seals New economical products for sealing construction joints.
openings as per the requirements of the Choose caulk or spray applied products tested to UL2079.
modified design.
CITY OF NEW YORK MEA 28-92M
Important Notice: All statements, technical information, and recommendations contained herein
Specified
are based upon testing believed to be reliable, but the accuracy and completeness thereof is not
guaranteed.
WARRANTY: Specified Technologies Inc. manufactures its goods in a manner to be free of defects.
Should any defect occur in its goods (within one year), Specified Technologies Inc., upon prompt
Technologies
notification, will at its option, exchange or repair the goods or refund the purchase price.
Limitations and Exclusions: THIS WARRANTY IS IN LIEU OF ALL OTHER
REPRESENTATIONS EXPRESSED OR IMPLIED (INCLUDING THE IMPLIED WARRANTIES OF
Inc.
MERCHANTABILITY OR FITNESS FOR USE) AND UNDER NO CIRCUMSTANCES SHALL
SPECIFIED TECHNOLOGIES INC. BE RESPONSIBLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL PROPERTY DAMAGE OR LOSSES. PRIOR TO USE, THE USER SHALL 200 Evans Way ?Somerville, NJ 08876
DETERMINE THE SUITABILITY OF THE PRODUCT FOR ITS INTENDED USE, AND THE USER
Phone: (800) 992-1180 ?Fax: (908) 526-9623
ASSUMES ALL RISKS AND LIABILITY FOR SUBSEQUENT USE.
Facts-On-Demand: (888) 526-6800
No statement or recommendation not contained herein shall have any force or effect unless in an
agreement signed by officers of seller and manufacturer.
STI on the WEB: www.stifirestop.com
MADE IN THE USA ?COPYRIGHT ?2000 SPECIFIED TECHNOLOGIES, INC.
Page 4 of 4 STI Product Data Sheet ?Series SSS Sealant FOD-5001 12/99
|